Technical Data Cable Carriers (CABLEVEYOR) - Cable carrier dedicated flexible cable - Technical notes
Sizing Standards
Cable selection table
For control 200 series |
For control / communication 400 series |
For electric power 400 series |
700 series | S700 series M700C series |
|
---|---|---|---|---|---|
Maximum allowable acceleration | 10m/s2 | 20m/s2 | 20m/s2 | 50m/s2 | 50m/s2 |
Maximum allowable speed (at short span) | 3.5m/s | 5m/s | 5m/s | 20m/s | 5m/s |
Maximum allowable speed (at long span) | 2m/s | 3.5m/s | 3.5m/s | 5m/s | 5m/s |
Travel distance Recommended range of use | 25m | 100m | 100m | 500m | 50m |
Operating Temperature Range | -5 ~ 80℃ | -5 ~ 80℃ | -5 ~ 80℃ | -35 ~ 90℃ | -35 ~ 90℃ |
Minimum bending radius (Without shield ) | 10 times or more of cabling outer diameter | 7.5 times or more of cabling outer diameter | 7.5 times or more of cabling outer diameter | 7.5 times or more of cabling outer diameter | Depending on the cable type |
Minimum bending radius (With shield ) | 10 times or more of cabling outer diameter | 7.5 times or more of cabling outer diameter | 7.5 times or more of cabling outer diameter | 7.5 times or more of cabling outer diameter | Depending on the cable type |
cURus certified | ○ | ○ | ○ | ○ | ○ |
Ultraviolet Resistant | Excellent | Excellent | Excellent | Acceptable (other colors) Excellent (black sheath) | Acceptable (other colors) Excellent (black sheath) |
Freon-free | ○ | ○ | ○ | ○ | ○ |
Flame-retardant | ○ | ○ | ○ | ○ | ○ |
Halogen-free | × | × | × | ○ | ○ |
Oil resistant | ○ | ○ | ○ | ○ | ○ |
Silicon free | ○ | ○ | ○ | ○ | ○ |
○: Supported ×: Not supported
Allowable current value
The values for allowable current (reference values) are based on an ambient temperature (in the air) of 30 °C and a maximum of three cores loaded simultaneously, when laid on the ground or grounded. For other conditions with different temperatures and energized core number, multiply by the conversion rates in the ambient temperature correction factor table and the core number correction factor table. (see DIN VDE 0298-4).
Allowable current (reference value)
Nominal cross-sectional area | Sheath | ||
---|---|---|---|
PVC | PUR | PUR (Single core ) |
|
0.75mm2 | 12A | 15A | |
1mm2 | 15A | 19A | |
1.5mm2 | 18A | 23A | 24A |
2.5mm2 | 26A | 32A | 32A |
4mm2 | 34A | 42A | 42A |
6mm2 | 44A | 54A | 54A |
10mm2 | 61A | 75A | 73A |
16mm2 | 82A | 100A | 98A |
25mm2 | 108A | 127A | 141A |
35mm2 | 135A | 158A | 176A |
50mm2 | 168A | 192A | 216A |
70mm2 | 207A | 246A | 279A |
95mm2 | 250A | 298A | 342A |
120mm2 | 292A | 346A | 400A |
150mm2 | 335A | 399A | 464A |
185mm2 | 382A | 456A | 533A |
240mm2 | 453A | 538A | 634A |
300mm2 | 523A | 621A | 736A |
400mm2 | 868A | ||
500mm2 | 998A |
Note) 1 The values in the tables are approximate values, and adopt the simplified form of DIN VDE 0298-4.
Note) 2 All values are general guidelines and are not intended for specific applications.
Ambient temperature correction factor
Ambient Temperature ℃ | Maximum cable operating temperature range | |||
---|---|---|---|---|
60℃ | 70℃ | 80℃ | 90℃ | |
10 | 1.29 | 1.22 | 1.18 | 1.15 |
15 | 1.22 | 1.17 | 1.14 | 1.12 |
20 | 1.15 | 1.12 | 1.10 | 1.08 |
25 | 1.08 | 1.06 | 1.05 | 1.04 |
30 | 1.00 | 1.00 | 1.00 | 1.00 |
35 | 0.91 | 0.94 | 0.95 | 0.96 |
40 | 0.82 | 0.87 | 0.89 | 0.91 |
45 | 0.71 | 0.79 | 0.84 | 0.87 |
50 | 0.58 | 0.71 | 0.77 | 0.82 |
55 | 0.41 | 0.61 | 0.71 | 0.76 |
60 | - | 0.50 | 0.63 | 0.71 |
65 | - | 0.35 | 0.55 | 0.65 |
70 | - | - | 0.45 | 0.58 |
75 | - | - | 0.32 | 0.50 |
80 | - | - | - | 0.41 |
85 | - | - | - | 0.29 |
Core number correction factor
(Applicable to multi-core cables up to a conductor nominal cross-sectional area of 10 mm 2 sup> )
Energized core number | Correction factor when installed in the air |
---|---|
5 | 0.75 |
7 | 0.65 |
10 | 0.55 |
14 | 0.50 |
19 | 0.45 |
24 | 0.40 |
40 | 0.35 |
61 | 0.30 |
Color code
DIN 47100 color code table
1 White | 11 Gray -Pink | 21 White -Blue | 31 Green -Blue | 41 Gray -Black |
2 Brown | 12 Red -Blue | 22 Brown -Blue | 32 Yellow -Blue | 42 Pink -Black |
3 Green | 13 White -Green | 23 White -Red | 33 Green -Red | 43 Blue -Black |
4 Yellow | 14 Brown -Green | 24 Brown -Brown | 34 Yellow -Red | 44 Red -Black |
5 Gray | 15 White -Yellow | 25 White -Black | 35 Green -Black | |
6 Pink | 16 Yellow -Brown | 26 Brown -Black | 36 Yellow -Black | |
7 Blue | 17 White -Brown | 27 Gray -Green | 37 Gray -Blue | |
8 Red | 18 Gray -Brown | 28 Yellow -Gray | 38 Pink -Blue | |
9 Black | 19 White -Pink | 29 Pink -Green | 39 Gray -Red | |
10 Purple | 20 Pink -Brown | 30 Yellow -Pink | 40 Pink -Red |
The first color represents the base color of insulator, and the second color represents the base color of the print ring.
AWG conductor diameter and cross-sectional area
AWG (American Wire Gauge) conversion table
AWG size | Diameter mm | Cross-sectional area mm2 | AWG size | Diameter mm | Cross-sectional area mm2 |
---|---|---|---|---|---|
500 | 20.7 | 254 | 16 | 1.29 | 1.31 |
400 | 18.9 | 203 | 17 | 1.15 | 1.04 |
350 | 17.3 | 178 | 18 | 1.024 | 0.823 |
300 | 16.0 | 152 | 19 | 0.912 | 0.653 |
250 | 14.6 | 127 | 20 | 0.812 | 0.519 |
4/0 | 11.68 | 107.2 | 21 | 0.723 | 0.412 |
3/0 | 10.4 | 85 | 22 | 0.644 | 0.325 |
2/0 | 9.27 | 67.5 | 23 | 0.573 | 0.259 |
0 | 8.25 | 53.4 | 24 | 0.511 | 0.205 |
1 | 7.35 | 42.4 | 25 | 0.455 | 0.163 |
2 | 6.54 | 33.6 | 26 | 0.405 | 0.128 |
3 | 5.83 | 26.7 | 27 | 0.361 | 0.102 |
4 | 5.19 | 21.2 | 28 | 0.321 | 0.0804 |
5 | 4.62 | 16.8 | 29 | 0.286 | 0.0646 |
6 | 4.11 | 13.3 | 30 | 0.255 | 0.0503 |
7 | 3.67 | 10.6 | 31 | 0.227 | 0.04 |
8 | 3.26 | 8.366 | 32 | 0.202 | 0.032 |
9 | 2.91 | 6.63 | 33 | 0.18 | 0.0252 |
10 | 2.59 | 5.26 | 34 | 0.16 | 0.04 |
11 | 2.3 | 4.15 | 35 | 0.143 | 0.0161 |
12 | 2.05 | 3.3 | 36 | 0.127 | 0.0123 |
13 | 1.83 | 2.62 | 37 | 0.113 | 0.01 |
14 | 1.63 | 2.08 | 38 | 0.101 | 0.00795 |
15 | 1.45 | 1.65 | 39 | 0.0897 | 0.00632 |
The first color represents the base color of insulator, and the second color represents the base color of the print ring.